Temperature Controller KT-310R
|
Parameter
|
Function
|
Set range
|
Default
|
|
E1
|
Lower set-point limit
|
-45℃/40℉~Set temp.
|
-35℃/-31℉
|
|
E2
|
Higher set-point limit
|
Set temp.~45℃/120℉
|
20℃/68℉
|
|
E3
|
Temp. Return Difference
|
1~10℃ / 1~18℉
|
4℃/7℉
|
|
E4
|
Comp.start delay time
|
0~10Min
|
2Min
|
|
E5
|
Room Temp. Calibration
|
-5~5℃/℉
|
0
|
|
E6
|
Evap.Temp. Calibration
|
-5~5℃/℉
|
0
|
|
F0
|
Defrost function
|
0=Electric heater 1=Hot gas
|
0
|
|
F1
|
Defrost Time
|
1~60Min
|
20Min
|
|
F2
|
Defrost Cycle
|
0~24Hr
|
6Hr
|
|
F3
|
Defrost termination temp.
|
0~20℃/ 32~68℉
|
8℃/46℉
|
|
F4
|
Display during defrost
|
0=Nomal display
1=Last value before defrost
|
0
|
|
F5
|
Fan operating function
|
0=Parallel with comp.
1=Continuous running except defrost
|
0
|
|
C1
|
Temperature unit
|
0=℃ 1=℉
|
0
|
|
C2
|
High temperature alarm
|
0~40℃/℉ above set-point
|
20
|
|
C3
|
Low temperature alarm
|
-40~0℃/℉ below set-point
|
-20
|
|
C4
|
Alarm time delay
|
1~90Min
|
60Min
|
|
|
|
|
| Specifications︰ | 1. Power Supply: Output transformer AC12V 2. Temperature sensor: NTC, Double sensors (for cold-room temp.&defrost control),2m(L) 3.Temp. measuring range: -45~45℃(-40~120℉); Accuracy:±1℃ (±2℉) 4. Temp. controlling range: -45~45℃ (-40~120℉); Factory default :0℃ (±32℉) 5. Dimension: 77 (L) × 35 (W) × 60(D) , Mounting Size: 71 (L) ×29 (W) mm 6. Operation environment: Temp.:-10~60℃ ( 14~140℉), Relative Humidity:20%~90%(No condensing) 7. Output contact capacity: Compressor: 20A/250VAC Defrost: 10A/250VAC Evap. Fan: 5A/250VAC
|